(To be performed ONLY by qualified service providers) Manual 47216A Save this manual for future referenceInstructions for:TTW 1 Universal ServiceRepla
TTW1 Universal ServiceReplacement BlowerMITW -10 SeriesPage 10Step 10. Now that the universal blower is properlymodified for a -10 series water heater
TTW1 Universal ServiceReplacement BlowerMITW -10 SeriesPage 11Step 14. If necessary, re-route the vent pipesuch that it can be properly seated inthe t
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 12Step 1. On the water heater’s gas control, turn thepower switch to the “Off” posit
Unplug blower harness fromjacket head receptacle bypinching the connector.Unscrew (3) screws that holdblower to the jacket head.Warning: Failure to lo
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 14Step 8. Install the flue restrictor, P/N239-47191-00, firmly on the flue. It mayb
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 15Step 9.b.) Inside the access compartment, follow the black wire from the power
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 16Step 9.f.) Verify that all electrical connections have been modified, as previo
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 17Step 12.a.) Position the junction box, P/N 239-47196-00, on top of the water
Route wiresthrough hole injunction box.Fasten connectorto junction box.Step 13. Locate new blower harness, P/N239-47194-00, provided with the kit.Rout
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 19Step 17. Secure the junction box cover, P/N239-47199-00, to the junction box.Step
Original Blower’s P/NWater Heater Model Numbers Serviced by This KitModel Numbers ReferencePage 2Water HeaterModel NumbersMITW -10SeriesMITW -12 / -15
TTW1 Universal ServiceReplacement BlowerMITW -12 / -15 SeriesPage 20Step 20. If it has not already been done, removethe old vent adapter from the exis
TTW1 Universal ServiceReplacement BlowerM1TW SeriesPage 21Step 1. On the water heater’s gas control, turn thepower switch to the “Off” position.Step 2
TTW1 Universal ServiceReplacement BlowerM1TW SeriesPage 22Unscrew both clamps thathold the adapter to theblower and vent pipe.Unscrew (3) screws that
TTW1 Universal ServiceReplacement BlowerM1TW SeriesPage 23Step 7.b.) Replace the current pressure switch ONLY IF the model is for high altitude
Step 8.b.) Place the access compartment cover back on the blower and secure it with its (3) screws from Step 7a. Start the lower screw fi
TTW1 Universal ServiceReplacement BlowerM1TW SeriesPage 25Step 9.c.) Replace the intake boot back onto the blower. If it is necessary, the cable,
TTW1 Universal ServiceReplacement BlowerM1TW SeriesPage 26Plug power cordback into outlet.Turn switch on gasvalve to “On” position.Step 12. Find the r
NotesPage 27NOTES
Part Number Qty Description Models Used On:1 265-47195-00 1 Universal Blower All2 239-47194-00 1 Wire Harness MITW-12/15 Series MITW -12 / -15 Series3
Tools RequiredPage 4¼" Nut Driver5/16" Nut DriverSlotted ScrewdriverPhilips ScrewdriverHammer1/8" Drill BitDrillChannel Lock PliersNeed
Bradford WhiteTTW 1 Universal ServiceReplacement Blower KitP/N 265-47200-00Table of ContentsPage 5Kit Components 3Tools Required 4MITW -10 Series Wate
TTW1 Universal ServiceReplacement BlowerMITW -10 SeriesPage 6Step 1. Unplug water heater from wall outlet.Step 2. Detach blower wire harness from rece
Step 6. Create the new mounting hole locationsfor the new universal replacement blower.Use template supplied with manual.a.) On the template, P/N 238-
TTW1 Universal ServiceReplacement BlowerMITW -10 SeriesPage 8Step 8. Instructions to remove power cord fromnew universal blower:a.) Unscrew the (3) Ph
TTW1 Universal ServiceReplacement BlowerMITW -10 SeriesPage 9Squeeze bushing toremove power cordfrom blower.Push in both sides ofthe bushing with plie