Servicing Guide continued-
When installing the control refer to the direction of the arrow on the hex and
insure that it is pointing upwards. If it is not pointing upward, the control
switch will not activate when the tank is refilled with water. Refer to Figure 7
for clarification.
Figure 7
Alarm Horn
The Alarm Horn is an option specified when the installation desires an
audible signal to immediately sound an alert when the water heater
operation is interrupted for certain faults. Referring to the control circuit
wiring diagram, the alarm will activate when any one of the following events
occur:
The Hi-Limit control has been tripped
The High Water Pressure Control senses excessive pressure
The Low Water Pressure Control senses insufficient pressure
The Low Water Level Control senses an insufficient quantity of water
The alarm will sound only for the options specified (i.e. if a low water level
control is not specified then the alarm will not recognize a low water level
condition). Referring to the Control Circuit Wiring Diagram, observe the horn
relay that is employed to correctly apply the horn to the control circuit.