Bradford White BWCH Operations Instructions Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
Page 46
BRADFORD WHITE CORP.
The control then operates the boiler stages to maintain
the programmed boiler target temperature. The reset
override operation is not affected by WWSD.
6.4.10 External Boiler Operation
When mode 6 is selected, the control allows for
an external control to operate the Copper Brute II’s
stages. In this mode, the control operates the pump in
order to provide purging and exercising. The staging
operation is provided by an external device such as
an Energy Management System (EMS) or External
Staging Control.
Heat Demand A heat demand is generated
when stage one is wired properly, and the external
control closes the contacts on the stage one terminals
(1C-1NO), calling the Copper Brute II for heat. The
Copper Brute II is shipped with a jumper between
the Com D and Ht D terminals, and this jumper must
remain in place when and external control is providing
the heat demand signal to these terminals. The control
energizes the boiler pump (if equipped), energizes
the Pmp-Pmp terminals, and turns on the boiler pump
segment in the display. The control also turns on
stage 1 of the boiler. Section 5.3 contains important
information about external staging controls and
building automation systems. Other wiring methods
may be unsafe. The wiring in Section 5.3 of this
manual must be used.
6.4.11 Limit Controls
In addition to the temperature control, Copper
Brute II appliances are tted with a manual reset
high limit and an automatic reset high limit. These
are located near the rear of the cabinet on the right
side, behind the slide out drawer (see Figure 32).
Both controls should be set at least 25°F higher than
the target temperature to avoid short cycling. To set
these controls, remove the control panel cover and
pull the control panel out to gain access. Appliances
with reversed heat exchangers have the limit controls
relocated to the left side of the appliance. The left
access door must be removed to gain access to the
limit controls on these appliances.
6.4.12 Advanced Programming Mode
Advanced programming mode allows the
installer to set the temperature control for proportional
staging. In advanced programming mode, the
interstage differential, interstage delay, interstage on
and off delay, and minimum time on and off are all set
manually.
NOTE: Advanced programming mode is rarely
required. It is intended for advanced installers,
and only when the application demands such
programming.
To enter advanced programming mode, remove
the bezel on the temperature control by pulling out at
the bottom. Remove the small phillips head screw to
access the dip switch. The dip switch is mounted on a
circuit board.
Locate the letter “A” on the circuit board and
slide the corresponding dip switch toward the letter
“A”. The default setting of this dip switch is toward
the
OFF lettering on the circuit board.
6.5 Operating the Burner and Set Up
6.5.1 Set Up for 0 to 2500 Feet Altitude
The Copper Brute II appliance utilizes a modular
design to achieve its stage-ring. The setup must be
checked before the unit is put in operation. Problems
such as failure to start, rough ignition, strong exhaust
odors, etc. can be due to improper setup. Damage to
the Copper Brute II resulting from improper setup is
not covered by the limited warranty.
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are
lled with water and all air has been bled from
both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. Switch on the appliance power switch located on
the right side of the unit.
5. The Copper Brute II will enter the start sequence,
as long as the unit is being called for heat. The
blower and pump come on for pre-purge, then
the ignitor warm-up sequence starts and after
the ignitor warm-up is complete and all safety
devices are veried, the gas valves open. If
ignition doesn’t occur, check that there is proper
gas supply. Wait 5 minutes and start the unit
again. During initial start up, air in the gas line
may cause the Copper Brute II to "lock out"
during the rst few trials for ignition. Depending
on the ignition modules installed, the manual
reset button on the ignition modules may need to
be depressed to restart the Copper Brute II.
6. When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not
exceed 13" w.c. (3.2kPa). The minimum inlet gas
pressure is 5" w.c. (1.2kPa).
7. Once the inlet gas pressure is veried, the
outlet gas pressure from each valve (manifold
gas pressure) must be checked, and adjusted, if
necessary. The manifold gas pressure must be
2.5" w.c. (0.62kPa).
8. Complete the setup by checking the CO
2
at the
outlet of the unit. The CO
2
should be 8% for
natural gas, or 9.2% for propane.
9. After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested.
To test:
(a) Close gas shutoff valve with burner
operating.
Page view 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 63 64

Comments to this Manuals

No comments