Bradford White BWCH Operations Instructions Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
Page 52
BRADFORD WHITE CORP.
8.6 Troubleshooting the Temperature
Control
See Table 12.
8.7 Troubleshooting Copper Brute II
Controls
The Copper Brute II series consists of two
2-stage models (500 and 750), one 3-stage model
(1000), and four 4-stage models (1250 to 2000). The
2-stage models have one ignition module, and the 3-
and 4-stage models have two ignition modules capable
of independent operation.
A diagnostic panel, that includes test points, as
well as diagnostic lights, is provided in the control
module. It is located on the right side of the module,
behind the display. To access, remove the retaining
screws from the display cover panel and remove
it. Grasp the control module at its base and pull it
outward. Ladder diagrams are shown in Figures 16
through 18. Voltage test points on the diagnostic
panel are indicated by solid circles connected by short
diagonal lines.
Figure 16 shows the diagram for the 2-stage sizes
500 and 750. These have one blower and one ignition
module. The blower is energized directly through the
“inducer” terminals F1 and F2 of the (Fenwal) ignition
module. The 24V power to the 2nd stage gas valve is
routed through the 1
st
stage VALVE terminal, so that
stage 2 cannot re unless the stage 1 gas valve is open.
The 750 differs from the 500 only in that the 750 has
two gas trains in stage 1, while the 500 has only one.
The ladder diagram for the size 1000 is shown
in Figure 17. Ignition module #1 handles stages 1 and
2, and ignition module #2 handles stage 3. The single
blower is energized directly through the “inducer”
terminals of either ignition module. The 24V power to
the T’STAT terminal of both ignition modules is routed
through the safety interlocks.
The ladder diagram for sizes 1250 to 2000 is
shown in Figure 18. These 4-stage models have two
ignition modules, each with its own blower, and each
controlling 2 stages. The blowers are energized by
the ignition modules indirectly via switching relays.
When either ignition module receives a call for heat, it
switches its blower to high speed and the blower of the
idle ignition module to low speed.
The wiring schematics for the Copper Brute II
500 – 1000 are shown in Figure 19, the schematics for
the 1250–1500 are shown in Figure 20, and Figure 21
shows the schematic for 1750–2000. All 24V wiring
is routed through the diagnostic PC board. Wiring
harnesses connect between the diagnostic PC board
and the control components, indicator board, or eld
wiring terminal strip. The diagnostic board contains
LEDs that indicate open status of the safety interlocks,
and quick-connect terminals that provide tests points
for checking voltage/continuity at various points in the
control circuit. Line-voltage connections are routed via
the line-voltage terminal buss.
Certain control elements that may need to be
re-wired in the eld are connected via the eld wiring
terminal strip rather than to the diagnostic PC board.
These include the low-water cutoff (LWCO), water
ow switch, and inlet/outlet water temperature sensors.